Field Controls

For proper operation and efficient fuel consumption in oil, gas, and/or coal-fired heating appliances, draft must remain constant. When it is, combustion is more complete, fuels are utilized efficiently, and money is saved.

Field Draft Controls maintain consistent draft by counteracting the negative forces caused by changes in temperature and barometric pressure, as well as the effects of wind.

Draft Inducers/Power Venters –

      With these devices, draft is increased or created, causing fluctuations in air flow through the combustion chamber. These fluctuations can be negated by the use of a barometric draft control located between the draft inducer or power venter and the furnace, boiler, or water heater it services. Use a single-acting control for oil and gas-fired equipment with a power vented system. Use a single acting control for oil, and a double-acting control for gas-fired equipment with a draft induced system.

Power Burners

      A power burner is designed so that a fan delivers negative air pressure to the combustion chamber. A single-acting draft control for oil maintains that negative pressure. A power burner designed to burn natural or LP gas operates in the same manner. While a draft hood (diverter) is often used on gas units fired with an atmospheric burner, a double-acting barometric draft control should be used for furnaces or boilers fired with power burners.

Forced Draft Burners

      Forced Draft installed with a stack height in excess of 30′ will probably develop excessive natural draft, reducing the amount of pressure within the furnace or boiler. A barometric draft control will help eliminate this undesirable stack action and permit the unit to be pressurized.

 

 